Introduction and Technical Analysis
Inverters, considered the heart of industrial automation systems, play an indispensable role in motor speed and torque control. One of the most critical power electronics components in these systems are IGBT (Insulated Gate Bipolar Transistor) modules. IGBT modules are used to convert DC voltage to AC voltage, providing controlled power to motors, thanks to their high switching speeds, low conduction losses, and high power density. A fault in an IGBT module can lead to the shutdown of the entire automation system, production losses, and significant costs. Therefore, the ability to quickly and accurately identify a faulty IGBT module in the field is vital for maintenance engineers and technicians. This guide provides an expert-level, step-by-step manual on how to diagnose an IGBT module fault using a multimeter. Our aim is to help professionals in the field minimize downtime by providing a reliable diagnostic method.
Operating Principle and Technical Data
An IGBT is a hybrid power semiconductor switching device that combines the high input impedance of a MOSFET and the low conduction losses of a bipolar transistor. It is essentially a voltage-controlled current device. The flow of current between the Collector and Emitter terminals is controlled by a voltage applied to the Gate terminal. In inverters, a three-phase bridge configuration consisting of six IGBTs is typically used. There is one upper and one lower IGBT for each phase. These IGBTs are switched by PWM (Pulse Width Modulation) signals, converting the DC bus voltage into an AC output voltage at the desired frequency and amplitude. Inside IGBT modules, a freewheeling diode is connected in parallel between the Collector and Emitter to protect the IGBT against sudden voltage surges. These diodes dissipate the energy stored by inductive loads (motor windings), protecting the IGBT and completing the current path during switching. An IGBT module fault is usually caused by factors such as overcurrent, overvoltage, overtemperature, incorrect gate driver signals, or mechanical stress. These conditions can cause the IGBT chip or its internal diodes to permanently short-circuit or open-circuit.
| Parameter | Value/Description |
|---|---|
| VCE(sat) (Collector-Emitter Saturation Voltage) | Typically between 1.5V – 4.0V (according to datasheet). |
| VGE(th) (Gate-Emitter Threshold Voltage) | Typically between 4.0V – 8.0V (minimum voltage required for switching). |
| IC(max) (Maximum Collector Current) | Varies according to module power (e.g., 50A, 100A, 400A). |
| Ptot (Total Power Loss) | Maximum power the module can dissipate (depends on heatsink). Must be checked against manufacturer datasheet values. |
| Diode Forward Voltage (VF) | Between 0.4V – 0.7V (for silicon diodes). This is the value seen with a multimeter. |
| Gate-Emitter Resistance (RGE) | Very high (several MΩ or open circuit – OL). It is a capacitive structure. |
| Tj(max) (Maximum Junction Temperature) | Generally between 125°C – 175°C. |

Field Considerations
- Safety is Always Paramount (LOTO): Inverters contain high DC bus voltage. Before attempting to service a faulty IGBT module, always de-energize the inverter (apply Lockout/Tagout procedures) and ensure that the DC bus capacitors are fully discharged. The discharge time may vary depending on the inverter’s power, typically 5-10 minutes is recommended. Confirm that the DC bus voltage has dropped to a safe level by checking with a voltmeter.
- Visual Inspection: Carefully inspect the IGBT module for signs of physical damage. Burn marks, exploded or swollen casing, cracks, melted terminals, or gel leakage indicate that the module is definitely faulty. Also, check the condition of the thermal paste on the heatsink.
- Environmental Conditions and Contamination: Assess whether the module’s environment is excessively dusty, humid, or exposed to chemical vapors. Contamination can lead to leakage currents or short circuits on the surface.
- Module Identification and Documentation: Note the exact part number of the module. Obtain the manufacturer’s technical datasheet. This is critical for understanding the correct pin connections (Collector, Emitter, Gate) and expected test values.
- Multimeter Selection and Settings: Use a reliable, True RMS digital multimeter. Diode test mode and resistance measurement mode are required for testing. Ensure your multimeter’s battery level is sufficient, as a low battery can lead to erroneous readings.
- Discharging the Gate Terminal: The Gate terminal of an IGBT has a capacitive structure, and accumulated static charge or residual voltage can lead to incorrect readings. Before starting the test, it is important to discharge the Gate by short-circuiting it to the Emitter (e.g., with a resistor or a short piece of wire). This ensures that the IGBT is completely in the off state.

Multimeter Health Check Steps
Checking the health of an IGBT module with a multimeter is typically done using the diode test mode. This mode allows us to assess the condition of the internal freewheeling diode and the IGBT’s own semiconductor structure.

1. Preparation and Safety
Fully implement the safety steps mentioned above (power cut, discharge). Disconnect the module from the inverter or at least de-energize the power terminals (DC bus and AC output). Correctly identify the Gate (G), Collector (C), and Emitter (E) terminals of the module. Markings are usually found on the module itself or can be checked from the datasheet.

2. Gate-Emitter (G-E) and Gate-Collector (G-C) Test
This test checks the insulation integrity of the Gate terminal and potential short circuits with the Gate driver circuit.
- Set the multimeter to diode test mode.
- Gate-Emitter (G-E):
- Connect the positive probe (red) of the multimeter to the Gate (G) terminal and the negative probe (black) to the Emitter (E) terminal. The display should show “OL” (Open Loop) or a very high resistance (several MΩ). This is because the Gate is a high-impedance and isolated structure relative to the Emitter.
- Reverse the probes (reverse polarity: red to E, black to G) and measure again. It should again show “OL” or a very high resistance.
- Expected Result: “OL” or very high resistance in both directions.
- Fault Indication: A low resistance reading (a few hundred ohms or less) or a diode drop (like 0.4-0.7V) indicates a short circuit or leakage between Gate and Emitter. This can cause the Gate driver circuit to fail or the IGBT to become uncontrollable.
- Gate-Collector (G-C):
- Repeat the same steps between the Gate (G) and Collector (C) terminals.
- Expected Result: “OL” or very high resistance in both directions.
- Fault Indication: A low resistance reading or a diode drop indicates a short circuit between Gate and Collector. This confirms that the module is faulty.

3. Collector-Emitter (C-E) Test (Internal Diode and IGBT Isolation)
This test checks the condition of the IGBT and the internal freewheeling diode. Remember, the Gate must be discharged.
- Keep the multimeter in diode test mode.
- Collector-Emitter (C-E) Forward Direction (Diode):
- Connect the positive probe (red) of the multimeter to the Emitter (E) terminal and the negative probe (black) to the Collector (C) terminal. This polarity forward-biases the internal freewheeling diode.
- Expected Result: The multimeter should show the forward voltage drop (VF) of the diode. This value will typically be between 0.4V and 0.7V (for silicon diodes). In some high-power modules, this value can go up to 1V.
- Fault Indication:
- “OL” reading: Indicates an open circuit in the internal diode. This also likely indicates that the IGBT is faulty.
- 0.000V or a very low value (less than 0.1V): Indicates a short circuit between the Collector-Emitter of the internal diode or the IGBT. This is one of the most common fault types.
- Collector-Emitter (C-E) Reverse Direction (IGBT and Diode Reverse Direction):
- Connect the positive probe (red) of the multimeter to the Collector (C) terminal and the negative probe (black) to the Emitter (E) terminal. This polarity reverse-biases the internal diode and checks the reverse blocking of the IGBT in the off state.
- Expected Result: The multimeter should show “OL” (Open Loop). This is because both the diode is reverse-biased and the IGBT is in the off state due to its discharged Gate, thus not conducting current.
- Fault Indication:
- Diode drop (like 0.4-0.7V) or a low resistance reading: Indicates a short circuit between Collector-Emitter. This confirms that the IGBT or the internal diode is faulty.
- A very low resistance (0.000V or a few ohms): Again, this is a short circuit fault.
4. Resistance Test Mode (Additional Check)
While the diode test mode is usually sufficient, in some cases, the resistance test mode can provide additional information.
- Set the multimeter to high resistance (MΩ) mode.
- Measure the resistance between all G-E, G-C, and C-E combinations.
- Expected Result: Very high resistance (several MΩ) or “OL” should be read in all combinations.
- Fault Indication: A low resistance reading (in the kiloohm or ohm range) indicates a short circuit or significant leakage between the respective terminals.
Common Issues and Solutions
IGBT module faults typically occur under specific scenarios and require specific resolution methods.
- Collector-Emitter Short Circuit: This is the most common fault type and usually occurs due to overcurrent, overvoltage, or thermal runaway. In multimeter testing, 0.000V or very low resistance is read between C-E in both directions.
- Solution: Replace the faulty IGBT module with a new one. After module replacement, it is crucial to check the inverter’s driver board and any issues on the load side (motor winding short circuit, mechanical jamming). Otherwise, the new module may also fail quickly.
- Collector-Emitter Open Circuit: While less common, it can occur, especially when bonding wires break due to overcurrent or mechanical stress. In multimeter testing, “OL” is read between C-E in both directions.
- Solution: Replace the module. An open circuit fault can often lead to the motor receiving single-phase power and producing abnormal noise when operating under load.
- Gate-Emitter or Gate-Collector Short Circuit/Leakage: This usually occurs due to faults in the Gate driver circuit (overvoltage, incorrect polarity) or degradation in the module’s internal structure. In multimeter testing, low resistance or a diode drop is read between G-E or G-C.
- Solution: Replace the module. Additionally, thoroughly check the inverter’s Gate driver board or optocouplers. A faulty Gate driver circuit can immediately cause the new IGBT module to fail as well.
- Thermal Paste Drying/Gaps: When heat transfer from the heatsink to the module is insufficient, the IGBT overheats, shortening its lifespan. This cannot be directly detected with a multimeter but can be identified by visual inspection.
- Solution: Always use new and high-quality thermal paste when replacing the module. Ensure the module sits perfectly on the heatsink by paying attention to mounting torque values. Check the ambient temperature and the efficiency of the cooling system.
- Parasitic Oscillations and Overvoltage Spikes: Inductive spikes generated during high-frequency switching can exceed the IGBT’s voltage withstand capability, leading to failure. This cannot be directly detected with a multimeter.
- Solution: Check the inverter’s DC bus capacitors and Snubber circuits. If necessary, optimize the DC bus voltage and switching frequency.
Expert Advice
IGBT modules are cornerstones of modern industrial automation, and their failures can lead to significant production downtimes. This detailed field guide provides a step-by-step methodology for quickly and reliably diagnosing IGBT module faults using a multimeter. Strict adherence to safety procedures, ensuring DC bus capacitors are discharged, and applying correct multimeter usage techniques are indispensable for successful fault detection. Specifically, diode and resistance tests between Gate-Emitter, Gate-Collector, and Collector-Emitter terminals provide critical information about the module’s internal integrity. It should be noted that while multimeter tests are highly effective in identifying “catastrophic” IGBT faults (short circuit or open circuit), more advanced tools like oscilloscopes or specialized testers may be required to detect more subtle or “intermittent” faults (e.g., leakages occurring at high temperatures or weakened switching performance). For field technicians and maintenance engineers, these basic multimeter tests are the first and most important step in making a quick preliminary diagnosis and preventing unnecessary part replacements. After a faulty module is replaced, finding and correcting the root cause of the fault (overload, faulty driver circuit, inadequate cooling, etc.) is critical for the future reliability of the system. Regular maintenance, monitoring of environmental conditions, and periodic inspection of critical components play a key role in extending the life of IGBT modules and minimizing unexpected failures. We hope the information in this guide will shed light on your valuable work in the industrial automation field and contribute to the uninterrupted operation of your systems. Request a quote on WhatsApp to learn more about our industrial CNC router solutions.
FAQ
How do I know if an IGBT module is faulty?
An IGBT module fault is typically identified by visual signs like burn marks, swollen casing, or cracks, or through electrical testing using a multimeter. Common electrical indications include a short circuit (0.000V or very low resistance) or an open circuit ("OL" reading) between Collector-Emitter, or a short/leakage between Gate-Emitter/Collector.
What safety precautions should be taken before testing an IGBT module?
Before testing, always ensure the inverter is de-energized (Lockout/Tagout) and DC bus capacitors are fully discharged. Visually inspect the module for damage. Use a reliable True RMS multimeter set to diode test mode. Discharge the Gate terminal by shorting it to the Emitter before testing.
What are the expected multimeter readings for a healthy IGBT module?
In diode test mode, measure between Gate-Emitter and Gate-Collector. You should see "OL" or very high resistance in both directions. For Collector-Emitter, in the forward direction (positive to Emitter, negative to Collector), you should see a diode voltage drop (0.4-0.7V). In the reverse direction (positive to Collector, negative to Emitter), you should see "OL".
What specific multimeter readings indicate an IGBT module fault?
A low resistance or diode drop between Gate-Emitter or Gate-Collector indicates a short circuit or leakage in the Gate. A 0.000V or very low resistance between Collector-Emitter in both directions indicates a short circuit. An "OL" reading between Collector-Emitter in the forward direction indicates an open circuit in the internal diode.
What should be done after identifying a faulty IGBT module?
If an IGBT module is found to be faulty, it must be replaced. Additionally, investigate the root cause of the failure, such as overcurrent, overvoltage, faulty Gate driver circuits, or inadequate cooling, to prevent recurring issues with the new module.